100 kW
Diesel Generators / 100REOZJD
Return to ResultsFeatures
- Kohler Co. provides one-source responsibility for the generating system and accessories.
- The generator set and its components are prototype-tested, factory-built, and production-tested.
- The 60 Hz generator set offers a UL 2200 listing.
- The generator set accepts rated load in one step.
- The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
- The generator set complies with ISO 8528-5, Class G2, requirements for transient performance in all generator set configurations. Select the Decision-MakerŪ 550 controller for improved voltage regulation and ISO 8528-5, Class G3, compliance.
- The 60 Hz generator set engine is certified by the Environmental Protection Agency (EPA) to conform to Tier 3 nonroad emissions regulations.
- A one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.
Alternator features:
- The unique Fast-Response(TM) II excitation system delivers excellent voltage response and short circuit capability using a permanent magnet (PM)-excited alternator.
- The brushless, rotating-field alternator has broad range reconnectability.
- NEMA MG1 ,IEEE, and ANSI standards compliance for temperature rise and motor starting.
- Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
- Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
- Self-ventilated and dripproof construction.
- Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life.
- Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
- Fast-Response(TM) II brushless alternator with brushless exciter for excellent load response.
Other features:
- Controllers are available for all applications.
- The low coolant level shutdown prevents overheating (standard on radiator models only).
- Integral vibration isolation eliminates the need for under-unit vibration spring isolators.
Specifications
| Prime Ratings: | 92 kW (115 kVa) | |
| Standby Ratings: | 100 kW (125 kVa) | |
| Hertz: | 60 Hz | |
| Alternator Type: | Brushless, Permanent-Magnet | |
| EPA Tier Level: | 3 | |
| Engine Manufacturer: | John Deere | |
| Engine Model: | 4045HF285I | |
| Cylinder Arrangement: | 4 Inline | |
| Max Power at Rated RPM: | 118 kWm (158 BHP) | |
| Prime Fuel Consumption at | ||
| 100% load: | 27.6 Lph (7.3 gph) | |
| 75% load: | 22.7 Lph (6 gph) | |
| 50% load: | 14.4 Lph (3.8 gph) | |
| 25% load: | 7.6 Lph (2 gph) | |
| Standby Fuel Consumption at | ||
| 100% load: | 31 Lph (8.2 gph) | |
| 75% load: | 25 Lph (6.6 gph) | |
| 50% load: | 17.8 Lph (4.7 gph) | |
| 25% load: | 9.5 Lph (2.5 gph) | |